|
|
|
Walls - Insulated Dry-Lining Plasterboard |
Plaster Dab
Bonding to Brick, Block and Concrete Masonry Cavity Walls
INTRODUCTION
For internal dry–lining applications, we recommend the use of Kingspan
Kooltherm K17 Insulated Dry-lining Board, an insulated
plasterboard laminate ideal for use in plaster dab bonded
dry–lining
applications. It is suitable for use with some solid walls and all
cavity masonry
wall constructions as well as timber frame walls. The boards are
as easy to handle as standard plasterboard and are fixed using similar
methods.
This method of wall insulation combines insulation, dry–lining and
vapour control in one board. Figure 1
|

|
|
PRODUCT DATA
|
ACHIEVING U–VALUES |
|

|
1 U–values
calculated assuming a Brick/Block or concrete masonry cavity wall.
For the purposes of these calculations
the standard of workmanship has been assumed good and therefore the
correction factor for air gaps ignored.
2
U–values calculated assuming a render finished dense block, cavity,
dense block wall. For the purposes of these calculations the standard
of workmanship has been assumed good and therefore the correction
factor for air gaps ignored.
3 Product thickness
= insulant thickness + 12.5 mm plasterboard.
4
l–value quoted is based on the procedures
for the determination of the aged values of thermal resistance and
thermal conductivity, laid down by the harmonised European standard
BS EN 13165, using so called 90/90 principles. Comparison with alternative
products may not be appropriate unless the same procedures have been
followed.
|
FIXING DETAILS
|
- A continuous fillet of Gypsum adhesive is applied at skirting
and ceiling level, as well as at openings to provide a continuous
seal.
- Apply further dabs of Gypsum adhesive in accordance with adhesive
manufacturers’ specification.
- Cut the boards to the height of the room, and place against
the adhesive dabs and tap back into correct position.
- Once plaster dabs have set, Gyproc nailable plugs are recommended
to be fixed at a rate of 3 per board. Two near the top of the
board and one centrally.
- At window, door reveals and soffits, narrow widths of board
should be cut to allow a plasterboard/plasterboard joint at an
angle to prevent cold bridging. These should be fixed in the same
way as for wall areas (see figure 2).
- Suitable mechanical fixings should be used for internal fittings
such as kitchen units, shelving etc… so that the load is applied
direct to the supporting wall and not the Kingspan Kooltherm
K17 Insulated Dry-lining Board.
- When refurbishing it is important to ensure all existing decoration
is removed on existing walls so that the plaster dab can form
a permanent bond.
- Cutting should be carried out using a fine toothed saw.
Boards may also be fixed using, adhesive bonding pads, please consult
the Kingspan Insulation Technical Services
Department for details.
|
| Figure
2 |
|
 |
|
| Insulated reveal detail |
|
|
|