INTRODUCTION
A partial fill cavity wall application provides the most effective
barrier to rain penetration by allowing the traditional wall cavity
to be maintained. The insulation is fixed to the inner leaf of the
wall construction, maintaining a clear cavity which avoids the problems
associated with full cavity fill. For this application we recommend
the use of KingspanKooltherm® K8 Cavity
Board (premium performance CFC–free rigid phenolic insulation).
Figure
1
PRODUCT DATA
ACHIEVING U–VALUES
KingspanKooltherm® K8
Cavity Board
Board Size
1.2 x 0.45
Insulant Thickness(mm)
Refer to local distributor or Kingspan Insulation price list
for current stock and non-stock sizes.
Facings
Composite Foil
Core
CFC/HCFC - free
rigid phenolic
To select the correct thickness
of
insulation to achieve a relevant U-value
please see
design tables below.
Thermal Conductivity
(l-value) - K8®
25-44mm 0.023W/m.K 45mm
0.022 W/m.K
1 The l–value quoted is in accordance
with the Harmonised European Standard BS EN
13166 (phenolic) using so called 90/90 principles. Comparison with
alternative products may not be appropriate unless the same procedures
have been followed.
FIXING DETAILS
Determine the overall cavity width by adding the thickness of
insulation required to the residual cavity width (50 mm minimum).
Install the first row of wall ties at 600 mm horizontal centres
to the inner leaf, one course of blockwork below the d.p.c. Install
the next course of blockwork to secure the ties.
Wall ties should include a retaining disc/clip and be of double
drip type, installed drip downward.
Continue constructing the inner leaf up to the next wall tie
course (450 mm above the first – usually 2 block courses). Position
the next course of wall ties at the usual 900 mm horizontal centres
and install the next course of blockwork to secure the ties.
The first row of insulation boards should now be installed,
ensuring each insulation board is retained tight against the inner
leaf at three points (this includes cut boards at details), see
figure 3.
Repeat the process described in the previous 2 bullet points.
Take care to remove excess mortar and protect the insulation
board edges from mortar snots by using a cavity board. (See figure
2).
Always ensure accurate trimming to achieve close butting joints
and continuity of insulation.
A vertical damp proof course should be installed at window and
door openings. The insulation boards can be used to prevent a
cold bridge at details. Refer to ‘Limiting thermal bridging and
air leakage: Robust construction details for dwellings and similar
buildings’, available from the Stationery Office.
When insulating to ceiling height at a gable, wall boards should
be continued 250 mm beyond the ceiling and a cavity tray installed
above the insulation.
Boards should be cut using a sharp knife or a fine toothed saw.
Figure
2
Figure 3
Use of a cavity
board to
protect the cavity
Boards are installed as work
proceeds
Easily achieve your required
thermal performance using KingspanKooltherm® K8 Cavity Board with any type of block.
For reasons of comparison the internal finish is taken as both 9.5
mm or 12.5 mm plasterboard on dabs and alternatively an internal finish
of lightweight plaster. See footnotes 1 and 2.
The table below, lists all the main block manufacturers in the UK
and the blocks they manufacture. To determine the thickness of insulation
you will need to achieve your required U–value, select the appropriate
block type and the corresponding thickness of insulation listed.
Dependent on the U–value required, the construction used for
the purposes of these calculations a 100 mm block inner (of thermal
conductivity shown in the table below), a minimum 50 mm cavity with
either rendered dense blockwork outer leaf for Scotland or a brickwork
outer leaf for England and Wales.
1 Add 5 mm to thickness of insulation
if using a 13 mm layer of lightweight plaster as a substitute for
the assumed 9.5 or 12.5 mm layer of plasterboard on dabs.
2 Add 5 mm to thickness of insulation if using a 13 mm layer of lightweight
plaster or 9.5 mm plasterboard on dabs as a substitute for 12.5 mm
layer of plasterboard on dabs.
3 For the purpose of these U–values we have assumed a rendered dense
blockwork outer leaf.
4 For the purpose of these U–values we have assumed a brickwork outer
leaf.
5 When calculating U–values to BS EN ISO 6946: 1997 the type of wall
tie used may change the thickness of insulation required. These
calculations
assume a stainless steel double triangle tie 3.7 mm diameter, giving
a cross sectional area of 10.75 mm². Contact the Kingspan
Insulation Technical Services Department for project calculations.
6 For the purposes of these calculations the standard of workmanship
has been assumed good and therefore the correction factor for air
gaps ignored.