New Build - Full Fill Between & Under Rafter Insulation
INTRODUCTION
This method of insulating is also suitable for existing buildings
where the tiles/slates need replacing. For this application we recommend
the use of KingspanKooltherm® K7 Pitched
Roof Board (premium performance CFC/HCFC–free rigid phenolic insulation)
with
KingspanKooltherm® K18 Insulated Dry-lining
Board beneath the rafters.
Figure
1
PRODUCT DATA
ACHIEVING U–VALUES
KingspanKooltherm® K7
Pitched Roof Board
Board Size
2.4 x 1.2
Insulant Thickness(mm)
Refer to local distributor or Kingspan Insulation price list
for current stock and non-stock sizes.
1 The requirement for a vapour control layer
and/or under tile ventilation should be assessed to BS 5250: 1989
(1995). Vapour check plasterboard or a separate vapour control layer
can be used as preferred.
2 Kingspan Kooltherm® K18 Insulated
Dry-lining Board contains an integral vapour control layer.
3 Calculations based on rafters being underlined
with Kingspan Kooltherm® K18 Insulated Dry-lining
Board comprising 12.5 mm plasterboard
and 25 mm insulation of thermal conductivity 0.022 W/m.K. Thickness
shown is between rafter component. All examples are based on 50 mm
wide rafters at 600 mm centres. For the purposes of these calculations
the standard of workmanship has been assumed good and the correction
factor for air–gaps ignored.
4 The l–value
quoted is in accordance with the Harmonised European Standard BS
EN 13166 (phenolic) using so called 90/90 principles. Comparison
with alternative products may not be appropriate
unless the same procedures have been followed.
5
If tiles are to be used then this normally necessitates the use of
counter battens and tiling battens over the breathable sarking membrane
to allow for water drainage and attachment of the tiles.
FIXING DETAILS
Between Rafter Insulation
Boards cut individually to fit the rafter spacings and simply
install the correct thickness of insulation in such a manner that
it is flush with the bottom of the rafters.
Measure the space between the rafters before cutting the boards
as spacings vary. In all cases ensure that insulation boards between
rafters are fitted tightly. Fill any gaps with expanding urethane
sealant.
Under Rafter Insulation
Fix the KingspanKooltherm® K18
Insulated Dry-lining Board at right angles to the underside of the rafters. Boards should
be fixed with galvanised clout nails, long enough to allow 25
mm penetration of timber. These should be placed at 150 mm centres
and not less than 10 mm from the edges of the board along all
supporting edges.
All edges of Kingspan Kooltherm® K18
Insulated Dry-lining Board must be supported. This will necessitate the use of noggings
placed between rafters to correspond with the long edges of the
boards.
General
Ensure accurate trimming to achieve close butting joints and
continuity of insulation.
Ensure the continuity of the insulation at the ridge.
To prevent a cold bridge, tightly pack flexible insulation material
between the rafters and the cavity closer.
Boards should be cut using a sharp knife or a fine toothed saw.